These installation cables according to VDE 0815 with electrostatic screen for industrial electronics are used telecommunication, measurement and information /data process systems.JE-H(St)H…Bd halogen free flame retardant cable type has low smoke emission and no corrosive gases during fire.
- Conductor Annealed Solid Copper (IEC/EN 60228)
- Insulation HFFR (EN 50290-2-26)
- Core Colors TS 13767, VDE 0815
- Lay-up 5 star quads laid up to a bundle, bundles laid up in layers
- Separator PET Foil
- Drain Wire Solid Tinned Copper Wire
- Screen Al-PET Foil
- Outer Sheath HFFR (EN 50290-2-27), RAL 7032 - Grey or RAL 3000 - Red
- Reference Standards TS 13767, VDE 0815
- Operating Voltage 300 V
- Test Voltage 800 V
- Insulation Resistance >100 M.Ωxkm
- Capacitance (@800Hz) ≤120 nF/km (capacitance values may increase by 20% up to 4 pair)
- Loop Resistance ≤73.2 Ω/km
- Temperature Range -30 °C........+70 °C
- Flame Retardancy IEC/EN 60332-1
- Smoke Density IEC/EN 61034-2
- Amount of Halogen Acid Gas IEC/EN 60754-1
- Corrosive Gases Measurement IEC/EN 60754-2
- Min. Bending Radius (Fixed) 8 x Cable Diameter