ÜRÜNLER
- Yangına Dayanıklı Kablolar
YSLYCY-JZ
These PVC cables (screened) are used in office equipment, electronic control systems, air condition systems, power stations, engineering projects for control, vision and measurement purposes. These can be used in wet or dry indoor applications. Screening protects the cable from the outer electrical effects.
- Conductor Stranded Annealed Copper (IEC/EN 60228, Class 5)
- Insulation PVC (EN 50290-2-21, TSE K 373)
- Core Colors Black (white numbered) Green-Yellow earth core in the outer layer (3 cores and above)
- Lay-up Cores are stranded in layers
- Inner Sheath PVC (EN 50290-2-22, EN 50363-4-1)
- Screen Tinned Copper Wire Braid
- Outer Sheath PVC (EN 50290-2-22, EN 50363-4-1), RAL 7001 - Grey
- Reference Standards TSE K 373
- Operating Voltage 0.50 mm²..1.50 mm² 300 V / 500 V; 2.50 mm²…... 450 V / 750 V
- Test Voltage 2500 V
- Conductor Resistance 0.50 mm² - ≤39 Ω/km; 0.75 mm² - ≤26 Ω/km; 1.00 mm² - ≤19.5 Ω/km; 1.50 mm² - ≤13.3 Ω/km; 2.50 mm² - ≤7.98 Ω/km
- Insulation Resistance >200 M.Ωxkm
- Transfer Impedance ≤250m Ω/m (30MHz)
- Temperature Range Fixed: -30 °C ........+70 °C, Flexible: -5 °C ........+70 °C
- Flame Retardancy IEC/EN 60332-1
- Min. Bending Radius Fixed: 10 x Cable Diameter, Flexible: 15 x Cable Diameter